Abstract
The voltage disturbances are compensated by a series-connected device called a dynamic voltage restorer (DVR) in a grid supply system. Three-phase DVR is operated with a proposed control based on zero-attracting LMS (ZA-LMS) for compensation of the voltage power quality (PQ) concerns. The ZA-LMS uses a variable step size for weight updating under dynamics. Second, the dc and ac link is associated with a severe voltage fluctuation, and it affects the performance of the DVR. To address this issue, an interval Type-2 fuzzy controller (IT2 FC) is developed and compared with a classical Type-1 fuzzy logic controller (T1 FLC). An osprey inspired optimizer (ISO) is utilized to achieve the optimum values of variables for T1 FLC and IT2 FC to accelerate the system response, save time, and achieve more accurate results. The parameters of antecedent and consequent are optimized by the ISO method, and observed that under a transitory scenario IT2 FC outperforms the T1 FLC with an improved response of settle time (T-s3), overshoot (O-s3), and undershoot (U-s3) of 0.121 s, 2.2%, and 5.6%, respectively. This shows that the IT2 FC yields potential results compared to conventional T1FC controllers under a dynamic environment. For validating the developed control schemes, simulation and experimentation results are demonstrated to show the efficacy of ZA-LMS integrated with IT2 FC under different grid conditions.